0577-27855777中文

YADE book - Download

YADE certificate - Download

Contact Us

Address: HOUJIE Industrial Zone,Liushi town,Yueqing County,Wenzhou city,Zhejiang province
TEL:0577-27855777 27855776
FAX:0577-27855778 27855775
EMAIL:cnyade@126.com
HTTP:www.cnyade.com
Zip code:325604
YADE ELEProduct Center
HOME > PRODUCT > Leakage circuit breaker
Product name:DZ30LE-32 DPN leakage circuit breaker
Product brand:Zhejiang YADE Electric Co. Ltd.
Product area: HOUJIE Industrial Zone,Liushi town,Yueqing County,Wenzhou city,Zhejiang province
Customer service:13706780110(Sales Manager)
Online consultation:点击这里给我发消息 亚德电气

First, the scope

DZ30LE-32 (DPN Vigi) (phase + neutral wire + leakage + overvoltage ) protection circuit breaker for AC 50Hz or 60Hz, rated voltage 230V, rated current up to 32A for single-phase residential lines, as the leakage protection, can also overload and short circuit protection of civil electrical lines, It can also pass off electrical installations and lighting circuit infrequently under normal circumstances, is especially suitable for industrial and commercial lighting distribution system, when the need to increase the over-voltage protection, over-voltage protection rating Uvo = 280V. The product has a small size, high breaking capacity; zero, FireWire and cut off, and in the case of reverse of the line of fire, can still be protected against leakage. This product meets the GB16917.1 standards. Electronic leakage overvoltage protection circuit breaker within the filter device, can prevent malfunction instantaneous voltage (lighting, other equipment line interference) and transient current (such as a large capacitive load line) caused tripping.
DZ30LE leakage protection switch in line with IEC61009-1 (1991), GB16917.1 (1997) and other standards. & nbsp;


Second, model and specification



Third, the structural characteristics

& nbsp; DZ30LE leakage circuit breakers is DZ30 breaker derived products, the overall structure with high breaking capacity, small size, structural characteristics of compact size, within four modulus (36mm) width, with two poles (P + N), phase, N pole and cut off, and the N pole has the advantage after the first turned off, the N line reversed phase, the remains leakage protection.
■ has a visible leakage operation indicator, green indicates no leakage fault, red indicates leakage fault. Using wire wiring, the maximum acceptable 16mm² round copper wire.
■ with the test device is equipped with a self-Duplex button, when pressed inside line to produce an analog residual current circuit breaker breaking. Test equipment should be regularly tested once a month.
■ use TH35-7.5 Standard steel mounting rail installation.


Fourth, the structural features

& nbsp; DZ30LE leakage circuit breaker is small, compact, cheaper than than similar products.
& nbsp; DZ30LE leakage circuit breaker housing and some functional parts are made of high fire-retardant, high temperature, high impact plastic .
& nbsp; DZ30LE leakage protection directly with the zero line installation, avoid wiring errors zero line potential shock hazard.
◆ DZ30LE leakage protection circuit design and using the latest high-performance components, when the impact of current and over-voltage surges, with a strong capacity, and does not cause malfunction.
& nbsp; DZ30LE GFCI using rail mounting, easy easy.


five main parameters and technical performance

◆ Product Category:
◇ according to the rated current of points; 6A, 10A, 16A, 20A, 25A, 32A.
◇ according to the number of poles is: with a protection of two-pole breaker pole (1P + N).
◇ type for the C-instantaneous release of (5ln ~ 10ln)
◇ Mechanical life: 2000 times.
◇ Electrical life: 3000 times.
◇ temperature environment: negative to positive forty five degrees Celsius.
◇ Rated voltage: AC 230V/400V & nbsp;
◇ rated insulation voltage: 500V


</tbody>
Rated voltage Ue (V) Poles frame degree rated current lnm (A) Rated Current ln (A) rated leakage current l △ n (mA) Rated residual non-operating current l △ no (mA) Rated residual breaking time (s) rated short-circuit breaking capacity lcn (A)
230 1P + N 32 6,10,16,20,25,32 30 15 ≤0.1 4500

test current Nominal voltage specified time Expected Results From initial state Notes
1.13 ln All values ​​ t≥1h not release cold current in 5s raised to a predetermined value is stable on the ground
1.45 ln All values ​​ t <1h trip Hot
2.55 ln All values ​​ 1 trip cold closed auxiliary switch power
5ln All values ​​ t≥0.1s not release cold closed auxiliary switch power
10ln All values ​​ t <0.1s trip cold closed auxiliary switch power

Six, shape and installation dimensions




Seven Note

DZ30LE -32 (DPN Vigi) (phase + neutral + leakage) protection filter device within the circuit breaker, can prevent malfunction instantaneous voltage (lighting, other line interference) and transient current (such as a large capacitive load line) caused tripping.

Eight, ordering instructions

when ordering indicate the following points:
Product type and name: If DZ30LE leakage protection /DZ30LE-32 leakage circuit breaker/DZ30 leakage switch.
Instantaneous tripping Current Rating: such as 32A.
Overvoltage protection when required, must be specified.
Order Number: as 2100.
Ordering example: DZ30LE leakage protection , 16A, 210 只.